Introduction
The MGate MB3660 (MB3660-8 and MB3660-16) gateways are redundant Modbus gateways that convert between the Modbus TCP and Modbus RTU/ASCII protocols. They can be accessed by up to 256 TCP master/client devices, or connect to 128 TCP slave/server devices. The MGate MB3660 isolation model provides 2 kV isolation protection suitable for power substation applications. The MGate MB3660 gateways are designed to easily integrate Modbus TCP and RTU/ASCII networks. The MGate MB3660 gateways offer features that make network integration easy, customizable, and compatible with almost any Modbus network. For large-scale Modbus deployments, MGate MB3660 gateways can effectively connect a large number of Modbus nodes to the same network.
The MB3660 Series can physically manage up to 248 serial slave nodes for 8-port models or 496 serial slave nodes for 16-port models (the Modbus standard only defines Modbus IDs from 1 to 247). Each RS-232/422/485 serial port can be configured individually for Modbus RTU or Modbus ASCII operation and for different baudrates, allowing both types of networks to be integrated with Modbus TCP through one Modbus gateway.
Certifications
Features
- Redundant Modbus gateway
- 2 x 10/100Mbps T(x) ports and 8 x RS-232/422/485 port
- 100 to 240 VAC dual input power
- Metal body
- 0 to 60°C operating temperature
industrial gateway : Ethernet Interface | |
Number of Ports | 2 (2 IP addresses) |
Speed | 10/100 Mbps, Auto MDI/MDIX |
Connector | RJ45 x 2 |
Protocols | Modbus TCP Client/Server |
industrial gateway : Serial port specifications | |
Protocols | Modbus RTU/ASCII Master/Slave |
RS-232 Signals | TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
Number of Ports | 8 |
RS-422 Signals | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-4w Signals | Tx+, Tx-, Rx+, Rx-, GND |
Serial Standards | RS-232/422/485, software selectable |
Connectors | DB9 male, RJ45 |
RS-485-2w Signals | Data+, Data-, GND |
RS-485 Data Direction Control | ADDC® (automatic data direction control) |
Isolation | 2 kV (for “-I” model) |
industrial gateway : Serial Communication Parameters | |
Data Bits | 7, 8 |
Stop Bits | 1, 2 |
Parity | Even, Odd, Space, Mark, None |
Flow Control | RTS/CTS, DTR/DSR, RTS Toggle (RS-232 only) |
Baudrate | 50 bps to 921.6 Kbps |
industrial gateway : Software | |
Configuration Options | Web conDevice Search Utility (DSU) for Windows 95, 98, ME, NT, 2000, Windows XP, Server 2003, Vista, Server 2008 (x86/x64), Windows Server 2008 R2, Windows 7/8/8.1/10 (x86/x64), Windows Server 2012 (x64), Windows 2012 R2sole, Serial console, Telnet console |
Utility | Device Search Utility (DSU) for Windows 95, 98, ME, NT, 2000, Windows XP, Server 2003, Vista, Server 2008 (x86/x64), Windows Server 2008 R2, Windows 7/8/8.1/10 (x86/x64), Windows Server 2012 (x64), Windows 2012 R2 |
Network Protocols | TCP/IP, UDP, HTTP, SMTP, NTP, DNS, DHCP Client, SNMPv1, ARP, Telnet, Radius |
industrial gateway : General | |
MTBF | 716,647 hrs |
industrial gateway : Power Requirements | |
Input Current | 144 mA @ 110 VAC, 101 mA @ 220 VAC |
Input Voltage | Dual 100 to 240 VAC, 47 to 63 Hz |
Power Connector | Terminal block (for DC models) |
industrial gateway : Physical Characteristics | |
Dimensions | Without ears: 440 x 45 x 198 mm (17.32 x 1.77 x 7.80 in), With ears: 480 x 45 x 198 mm (18.90 x 1.77 x 7.80 in) |
Housing | Metal, IP30 |
Operating Temperature | 0 to 60°C (32 to 140°F) |
Weight | 2,731 g (6.02 lb) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Vibration | IEC 60068-2-6, IEC 60068-2-64 |
Shock | IEC 60068-2-27 |
Drop | IEC 60068-2-32 |
Safety | UL 60950-1, EN 60950-1 (LVD) |
EMC | EN 55032/24 |
EMI | CISPR 32, FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV, IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m, IEC 61000-4-4 EFT: Power: 1 kV; Signal: 1 kV, IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV, IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10V/m, IEC 61000-4-8 PFMF |